KNX DIN Heating Actuator 8 In / 8 Out

173,00 Excl. tax €307,00 Excl. tax
€209,33 Incl. tax 371,47 Incl. tax.
Out of stock, but available
Unit price: €173,00 / Piece
KNX DIN rail actuator with 8 triac outputs for electrothermal valves and 8 configurable inputs. Supports on/off, PWM and 3-point control, with integrated thermostat modules and logic functions for HVAC systems. Read more

Specifications

Brand:
eelectron
Article number:
HA08A01KNX
EAN:
8054144521169
Availability:
Out of stock, but available
Delivery time:
Dispatched within approximately 8 working days (please note: this is an estimate and depends on availability from the manufacturer; in some cases, it may be dispatched sooner, but it can also take longer).
Due to the holidays, orders may be delayed and pickup is not possible.

Information

Link to eelectron website (English)

KNX DIN Heating Actuator 8 In / 8 Out

Art. No.: HA08A01KNX

This KNX DIN rail heating actuator is designed for the control of electrothermal valves in heating and cooling systems. The device features 8 triac outputs and 8 freely configurable inputs and is suitable for professional HVAC applications within KNX installations in residential and commercial buildings.

The outputs can be individually configured as 8 channels for on/off control or PWM control, or as 4 channels for 3-point valve control. This makes the actuator highly versatile for applications such as underfloor heating, radiators, fan coil systems (2- and 4-pipe) and zone heating.

The 8 inputs are intended for potential-free contacts and can be used for switches, push-buttons, scenes, shutter and blind control, sequences and step commands. In addition, inputs 1 to 4 can be configured as outputs for signalling LEDs or as analogue inputs for NTC temperature sensors.

The actuator provides extensive integrated thermostat functionality. A total of 8 thermostat modules are available, with each module managing 2 control stages using an integrated PI controller. This enables precise control of heating and cooling systems, valves and fan coils.

Furthermore, 8 logic blocks are available to implement simple logical functions or more complex calculations using algebraic and conditional operators. Predefined algorithms are also available, such as proportional temperature and humidity control and dew point calculation.

Technical specifications

  • KNX / EIB communication interface
  • Mounting: DIN rail (4 modules wide)
  • Power supply: via KNX bus, 21 – 32 V DC
  • Current consumption: ≤ 15 mA
  • Number of outputs: 8 triac outputs
  • Output voltage: 24 – 230 V AC, 50/60 Hz
  • Rated current per output: 500 mA
  • Inrush current (per group of 4): max. 4 A
  • Number of inputs: 8 potential-free inputs
  • Support for NTC temperature sensors
  • Maximum cable length of inputs: 30 m (twisted)
  • Operating temperature: -5 °C to +45 °C
  • Degree of protection: IP20
  • Relative humidity: max. 90% (non-condensing)