KNX DALI Gateway TW, 1 channel

428,00 Excl. tax €475,00 Excl. tax
€517,88 Incl. tax 574,75 Incl. tax.
Out of stock, but available
Unit price: €428,00 / Piece
Universal KNX-DALI gateway with 1 channel for controlling up to 64 DALI ECGs. Supports Tunable White (DT-8), group control, scenes, time scheduling and fault diagnostics via KNX. Read more

Specifications

Brand:
eelectron
Article number:
IC01D01DAL
EAN:
8054144522937
Availability:
Out of stock, but available
Delivery time:
Dispatched within approximately 8 working days (please note: this is an estimate and depends on availability from the manufacturer; in some cases, it may be dispatched sooner, but it can also take longer).

Information

Link zur Website von eelectron (Englisch)

Universal KNX DALI Gateway TW – 1 Channel

Part number: IC01D01DAL  |  EAN: 8054144522937

The Eelectron IC01D01DAL is a universal KNX–DALI gateway with one channel (Single-Master Application Controller) designed to control electronic ballasts (ECGs) with a DALI interface according to EN 62386. The device converts KNX switch and dim commands into DALI telegrams and sends DALI status information back to the KNX bus. One DALI output supports up to 64 ECGs, either individually or in up to 16 DALI groups. It supports Tunable White (DT-8) lighting and integrates KNX scenes, time programs, and colour control through DALI.

Applications

  • KNX–DALI integration for office, retail, and commercial lighting systems
  • Tunable White (DT-8) and colour control via KNX scenes and time schedules
  • Group and broadcast control with manual operation directly on the device
  • Monitoring, fault detection, and maintenance planning (operating hours counter per group/ECG)

Main features

  • 1× DALI output, up to 64 ECGs (individual or 16 groups)
  • Tunable White / DT-8 and colour light control (Device Type 8) depending on sub-type:
    • Tc (Correlated Colour Temperature)
    • XY (xy colour coordinates)
    • RGB / RGBW / HSV (DT-8 sub-type RGBWAF)
    DT-8 sub-type PrimaryN is not supported.
  • ETS5 commissioning via DCA (Device Control App) with flexible addressing and setup
  • Scenes and time scheduling for groups and individual ECGs (value and/or colour based)
  • Operating modes: permanent, night-time, or staircase function
  • Operating hours counter per group/ECG with alarm for lifetime limit reached
  • Fault management: individual fault objects per ECG, detailed analysis by group/device, fault counting and threshold monitoring
  • Scene module with dimmable scenes; “Quick exchange” function for fast replacement of defective ECGs
  • Manual operation (group and broadcast telegrams) via front buttons; LED indicators for status and fault messages

DALI and compatibility information

  • Supports ECGs compliant with EN 62386-102 ed.1 (DALI v1) and ed.2 (DALI-2)
  • Certified according to EN 62386-101 and -103 ed.2 (DALI-2); authorised to bear the DALI-2 logo
  • Single-master operation only: no additional DALI controllers within the same segment. The device provides its own DALI power supply; external DALI supply is not permitted
  • DT-1 emergency lighting devices can be read and switched, but test and report functions are not supported. For full DT-1 operation, use the IC01D03DAL

Technical specifications

Operating voltage (mains) 110–240 V AC or DC, 50–60 Hz
Power consumption Max. 9 W
KNX bus SELV 24 V DC, approx. 5 mA; medium: Twisted Pair (TP)
DALI outputs 1× Single-Master Application Controller (EN 62386-103 ed.2)
Max. number of ECGs 64 (individual or grouped into 16 groups)
DALI supply voltage Typical 16–18 V DC, short-circuit proof; guaranteed 128 mA, max. 250 mA (basic insulation, not SELV)
Shutdown delay 600 ms after short-circuit detection
Restart delay 5 s after shutdown
Terminals (mains) L/N/PE, screw terminals, 3× 1–2.5 mm² (solid or stranded)
Terminals (DALI) D+ / D-, screw terminals, 2× 1–2.5 mm², recommended minimum 1.5 mm²
KNX connection Bus connector, spring terminal 0.6–0.8 mm (solid)
Control elements Prog button (KNX), 1× manual button, 8× group/broadcast/service buttons
Indicators Red LED (normal/address mode); RGB LED (manual/fault); 8× red LEDs (group status/fault)
Housing ABS V0, 4 DIN modules, approx. 130 g
Mounting 35 mm DIN rail (low-voltage distribution board)
Protection rating IP20 (EN 60529)
Protection class Class I (IEC 1140)
Overvoltage category Cat. III
Pollution degree Class 2
Standards & directives EN 62386-101/-102/-103, EN 63044-5-3; LVD 2014/35/EU; UK S.I. 2016:1101

Important notes

  • Single-master operation: use only one DALI controller per segment; external DALI supplies are not allowed.
  • Integrated DALI power supply: the gateway powers the DALI line; observe current and cable length limits.
  • DT-8 sub-type PrimaryN is not supported; use Tc/XY/RGB(RGBW/HSV) depending on ECG specification.
  • For DT-1 emergency lighting with test/report functions, use IC01D03DAL.
  • Installation, commissioning and ETS configuration must be performed by qualified professionals in accordance with KNX/DALI standards and safety regulations.