KNX DALI Gateway – 2 Channels
€617,00 Excl. tax
€685,00 Excl. tax
€746,57 Incl. tax €828,85 Incl. tax. Out of stock, but available
Unit price: €617,00 / Piece
€746,57 Incl. tax €828,85 Incl. tax. Out of stock, but available
KNX-DALI gateway with 2 independent channels controlling up to 128 ECGs (64 per channel). Supports Tunable White (DT-8), scenes, time schedules and fault diagnostics via KNX. Read more
Specifications
Brand:
eelectron
Article number:
IC02D01DAL
EAN:
8054144522234
Availability:
Out of stock, but available
Delivery time:
Dispatched within approximately 8 working days (please note: this is an estimate and depends on availability from the manufacturer; in some cases, it may be dispatched sooner, but it can also take longer).
Information
Link zur Website von eelectron (Englisch)
KNX DALI Gateway TW – 2 Channels
Article number: IC02D01DAL | EAN: 8054144522234
The Eelectron IC02D01DAL is a universal KNX–DALI gateway featuring two completely independent channels (Single Master Application Controllers) for controlling electronic ballasts (ECGs) with a DALI interface according to EN 62386. Each channel supports up to 64 ECGs, individually or divided into up to 16 DALI groups, allowing control of up to 128 devices via a single gateway. The device supports Tunable White (DT-8) and DALI-2 lighting control and provides integrated power supply for connected ECGs – no external DALI supply is required or allowed.
Applications
- KNX–DALI integration for lighting control in offices, public buildings and commercial environments
- Control of Tunable White (DT-8) and dynamic RGB/colour lighting via KNX
- Scene recall, scheduling and group management for energy-efficient lighting
- Fault monitoring, operating hours counter and maintenance tracking via KNX
- Mounting on DIN rail (35 mm) in low-voltage distribution boards
Main features
- 2 independent DALI outputs – each for up to 64 ECGs (DALI/DT-8 compatible)
- Tunable White (DT-8 Sub-Type Tc) and colour control (XY, RGB, HSV, RGBW)
- Full DALI-2 support according to EN 62386-101/-102/-103 ed.2
- Complete ETS5 configuration via DCA (Device Control App)
- Addressing of up to 16 groups per output
- Scene control with dimming and time-based colour or value settings
- Operating hours counter per group/ECG with lifetime alarm
- Individual fault detection for each light/ECG with detailed group analysis
- Threshold monitoring with configurable fault limits
- “Quick Exchange” function for easy replacement of defective ECGs
- Manual control of group and broadcast telegrams via front buttons
- LED indicators for mode, fault and group status (red/green/blue)
DALI and compatibility
- Single Master Application Controller – multi-master operation not allowed
- Supports ECGs according to EN 62386-102 ed.1 (DALI v1) and ed.2 (DALI-2)
- Certified according to EN 62386-101 and -103 ed.2 (DALI-2, DIIA certified)
- Supports Device Type 8 (DT-8) for Tunable White and colour management
- Supports subtypes XY, Tc, RGB, HSV, RGBW (PrimaryN not supported)
- Reads and controls DALI DT-1 emergency lighting devices (without test report functions)
Technical specifications
Power supply (mains) | 110–240 V AC/DC, 50–60 Hz |
---|---|
Power consumption | Max. 16 W |
KNX bus supply | SELV 24 V DC, approx. 5 mA |
Number of DALI outputs | 2 (Single Master Application Controllers, EN 62386-103 ed.2) |
Maximum number of ECGs | 64 per output (128 total) |
DALI voltage | Typical 16–18 V DC, short-circuit proof, basic insulation (no SELV) |
Guaranteed current | 128 mA |
Maximum current | 250 mA |
Shutdown delay | 600 ms after short-circuit detection |
Restart delay | 5 s after short-circuit recovery |
Control elements | Programming button (KNX), manual mode button, 8 function keys |
Indicators | LED red/green/blue (mode, error, status) + 8 red LEDs (group status) |
Housing | ABS V0 plastic, 4 DIN modules |
Mounting | DIN rail (35 mm) according to EN 60715 |
Weight | Approx. 130 g |
Protection class | Class I according to IEC 1140 |
Protection rating | IP20 according to EN 60529 |
Overvoltage category | Category III |
Pollution degree | Class 2 (EN 60664-1) |
Operating temperature | -5 °C … +45 °C |
Storage temperature | -25 °C … +55 °C |
Relative humidity | 5% – 93% (non-condensing) |
Standards and directives | EN 62386-101/-102/-103, EN 63044-5-3, EMC 2014/30/EU, LVD 2014/35/EU |
Important notes
- Only one DALI controller per segment (multi-master operation not supported).
- The integrated DALI power supply provides current to the connected ECGs – external DALI supplies are not permitted.
- The DT-8 PrimaryN subtype is not supported.
- For full DT-1 emergency lighting functionality, the IC01D03DAL model is recommended.
- Installation and configuration must be carried out by qualified personnel according to KNX and DALI standards.