KNX DALI Gateway – 2 Channels

617,00 Excl. tax €685,00 Excl. tax
€746,57 Incl. tax 828,85 Incl. tax.
Out of stock, but available
Unit price: €617,00 / Piece
KNX-DALI gateway with 2 independent channels controlling up to 128 ECGs (64 per channel). Supports Tunable White (DT-8), scenes, time schedules and fault diagnostics via KNX. Read more

Specifications

Brand:
eelectron
Article number:
IC02D01DAL
EAN:
8054144522234
Availability:
Out of stock, but available
Delivery time:
Dispatched within approximately 8 working days (please note: this is an estimate and depends on availability from the manufacturer; in some cases, it may be dispatched sooner, but it can also take longer).

Information

Link zur Website von eelectron (Englisch)

KNX DALI Gateway TW – 2 Channels

Article number: IC02D01DAL  |  EAN: 8054144522234

The Eelectron IC02D01DAL is a universal KNX–DALI gateway featuring two completely independent channels (Single Master Application Controllers) for controlling electronic ballasts (ECGs) with a DALI interface according to EN 62386. Each channel supports up to 64 ECGs, individually or divided into up to 16 DALI groups, allowing control of up to 128 devices via a single gateway. The device supports Tunable White (DT-8) and DALI-2 lighting control and provides integrated power supply for connected ECGs – no external DALI supply is required or allowed.

Applications

  • KNX–DALI integration for lighting control in offices, public buildings and commercial environments
  • Control of Tunable White (DT-8) and dynamic RGB/colour lighting via KNX
  • Scene recall, scheduling and group management for energy-efficient lighting
  • Fault monitoring, operating hours counter and maintenance tracking via KNX
  • Mounting on DIN rail (35 mm) in low-voltage distribution boards

Main features

  • 2 independent DALI outputs – each for up to 64 ECGs (DALI/DT-8 compatible)
  • Tunable White (DT-8 Sub-Type Tc) and colour control (XY, RGB, HSV, RGBW)
  • Full DALI-2 support according to EN 62386-101/-102/-103 ed.2
  • Complete ETS5 configuration via DCA (Device Control App)
  • Addressing of up to 16 groups per output
  • Scene control with dimming and time-based colour or value settings
  • Operating hours counter per group/ECG with lifetime alarm
  • Individual fault detection for each light/ECG with detailed group analysis
  • Threshold monitoring with configurable fault limits
  • “Quick Exchange” function for easy replacement of defective ECGs
  • Manual control of group and broadcast telegrams via front buttons
  • LED indicators for mode, fault and group status (red/green/blue)

DALI and compatibility

  • Single Master Application Controller – multi-master operation not allowed
  • Supports ECGs according to EN 62386-102 ed.1 (DALI v1) and ed.2 (DALI-2)
  • Certified according to EN 62386-101 and -103 ed.2 (DALI-2, DIIA certified)
  • Supports Device Type 8 (DT-8) for Tunable White and colour management
  • Supports subtypes XY, Tc, RGB, HSV, RGBW (PrimaryN not supported)
  • Reads and controls DALI DT-1 emergency lighting devices (without test report functions)

Technical specifications

Power supply (mains) 110–240 V AC/DC, 50–60 Hz
Power consumption Max. 16 W
KNX bus supply SELV 24 V DC, approx. 5 mA
Number of DALI outputs 2 (Single Master Application Controllers, EN 62386-103 ed.2)
Maximum number of ECGs 64 per output (128 total)
DALI voltage Typical 16–18 V DC, short-circuit proof, basic insulation (no SELV)
Guaranteed current 128 mA
Maximum current 250 mA
Shutdown delay 600 ms after short-circuit detection
Restart delay 5 s after short-circuit recovery
Control elements Programming button (KNX), manual mode button, 8 function keys
Indicators LED red/green/blue (mode, error, status) + 8 red LEDs (group status)
Housing ABS V0 plastic, 4 DIN modules
Mounting DIN rail (35 mm) according to EN 60715
Weight Approx. 130 g
Protection class Class I according to IEC 1140
Protection rating IP20 according to EN 60529
Overvoltage category Category III
Pollution degree Class 2 (EN 60664-1)
Operating temperature -5 °C … +45 °C
Storage temperature -25 °C … +55 °C
Relative humidity 5% – 93% (non-condensing)
Standards and directives EN 62386-101/-102/-103, EN 63044-5-3, EMC 2014/30/EU, LVD 2014/35/EU

Important notes

  • Only one DALI controller per segment (multi-master operation not supported).
  • The integrated DALI power supply provides current to the connected ECGs – external DALI supplies are not permitted.
  • The DT-8 PrimaryN subtype is not supported.
  • For full DT-1 emergency lighting functionality, the IC01D03DAL model is recommended.
  • Installation and configuration must be carried out by qualified personnel according to KNX and DALI standards.