BM 6 T KNX 6-fold binary input 10 V DC – 240 V AC with LED
€151,07 Excl. tax
€262,73 Excl. tax
€182,79 Incl. tax €317,90 Incl. tax. Out of stock, but available
Unit price: €151,07 / Piece
€182,79 Incl. tax €317,90 Incl. tax. Out of stock, but available
6-fold binary input with LED status per channel, manual control, input voltage 10 V DC – 240 V AC, suitable for DIN rail mounting. Read more
Specifications
Brand:
Theben
Article number:
4940230
EAN:
4003468490716
Availability:
Out of stock, but available
Delivery time:
Will be shipped within approximately 8 working days.
Information
BM 6 T KNX – 6-fold binary input FIX1
Item no. 4940230
Application
The BM 6 T KNX is a 6-fold binary input for use in KNX systems. This FIX1 module is suitable for DIN rail mounting and processes digital signals with input voltages from 10 V DC to 240 V AC. Each input features an LED indicator for status display. Manual operation is also possible without bus voltage.
Functions
- 6-fold binary input for signal voltages from 10 V DC to 240 V AC
- LED status indication for each channel
- Manual operation directly on the device, even without KNX bus voltage
- DIN rail mounting (4 modules width)
- Suitable for signals from switches, push-buttons or volt-free contacts
- Output: 12 V DC / 18 mA SELV
- Standard KNX bus terminal for easy integration
Technical specifications
- KNX supply current: ≤ 4 mA
- Additional power supply: 110 V AC – 240 V AC, 50–60 Hz
- Frequency: 50–60 Hz
- Standby power consumption: ~0.3 W
- Input voltage: 10 V DC – 240 V AC, 2 mA
- Number of inputs: 6
- Output: 12 V DC / 18 mA, SELV
- Display: 6 LEDs to indicate input status
- SELV compliant: Yes, if SELV voltage is applied to all inputs
- Maximum cable length: 100 m
- Connection type: KNX terminal, screw terminals
- Cable cross-section:
- Solid: 0.5 mm² (Ø 0.8 mm) to 6 mm²
- Stranded with ferrule: 0.5 mm² to 4 mm²
- Mounting: DIN rail, 4 modules wide
- Ambient temperature: -5 °C to +45 °C
- Protection rating: IP 20
- Protection class: II according to EN 60730-1
Important notes
- For SELV use, all inputs must be supplied with SELV voltage.
- Manual control is possible even without bus voltage.
- Not suitable for analog signals – only digital switching signals are supported.