theMura P180 2.20 KNX UP WH – PIR sensor, 2 light & 2 HVAC channels

93,42 Excl. tax €162,48 Excl. tax
€113,04 Incl. tax 196,60 Incl. tax.
Out of stock, but available
Unit price: €93,42 / Piece
Wall-mounted presence detector (2.2 m) with 170° coverage, 2 light and 2 HVAC channels, integrated sensors and KNX Data Secure. Flexible lighting and climate control. Read more

Specifications

Brand:
Theben
Article number:
2069658
EAN:
4003468200629
Availability:
Out of stock, but available
Delivery time:
Dispatched within approximately 8 working days (please note: this is an estimate and depends on availability from the manufacturer; in some cases, it may be dispatched sooner, but it can also take longer).

Information

Link to Theben website

theMura P180 2.20 KNX UP WH

Presence detector with 2 light and 2 HVAC channels,

Art. no.: 2069658

Application

This passive infrared presence detector for flush wall mounting is designed for KNX building automation. The device offers a rectangular detection area of 170° and up to 16 x 10 m (160 m²) at a mounting height of 2.2 meters. It is ideal for reliable detection and automatic control of lighting and climate installations in offices, corridors, meeting rooms, and other commercial buildings.

Features

  • Rectangular detection area of 170°, 16 x 10 m (160 m²) at 2.2 m mounting height
  • 2 light channels and 2 HVAC channels, suitable for the KNX bus system
  • KNX Data Secure for safe communication within the KNX network
  • Switching or constant light control possible, with standby function (orientation light)
  • Dimmable lighting when switching, with or without daylight influence
  • Easy correction of brightness measurement
  • Short presence and selectable control speed
  • Aura function and scene functions for flexible automation
  • Integrated orientation light (white)
  • Integrated temperature sensor
  • Acoustic function
  • 2 binary inputs for external switches or sensors
  • 6 logic channels (AND, OR, XOR) for complex logic
  • Limited settings via theSenda B (app/universal remote control) and theSenda P (service remote control)
  • Optional user remote control (theSenda S/B) for manual override
  • Fully or semi-automatic operation possible
  • Integrated freely configurable button (can be deactivated)
  • Manual override via external KNX button possible
  • Targeted brightness measurement (mixed light measurement)
  • Learning function and blocking functions
  • HVAC channel without brightness influence, switch-on delay and follow-up time adjustable
  • Detection area can be expanded via Master/Slave or Master/Master parameter settings
  • Adjustable detection sensitivity
  • Test mode for checking functions and detection area
  • Settings via ETS software (full functionality)
  • Detection area limitation strips included
  • Suitable for Theben cover frames and many common switch ranges (with accessories)

Technical Specifications

Brightness measurement range 5 - 3000 lx
Mounting type Wall mounting (flush-mounted)
Detection area Rectangular, 170°, 16 x 10 m (160 m²) at 2.2 m mounting height
Light follow-up time 30 seconds - 60 minutes
Type of light measurement Mixed light measurement
Presence follow-up time 10 seconds - 120 minutes
Ambient temperature -15°C to +45°C
Color White
Protection class IP 20
KNX Data Secure Yes
Light channels 2
HVAC channels 2
Binary inputs 2
Logic channels 6 (AND, OR, XOR)
Orientation light Integrated (white)
Temperature sensor Integrated
Acoustic function Yes
Mounting accessories Compatible with various switch ranges (accessories)
Predecessor 2009050, PresenceLight 180B-KNX WH

Important Notes

  • Full functionality can only be configured via ETS software.
  • Limited local control via remote control theSenda B/P or user remote theSenda S/B.
  • For indoor use only (IP20), not suitable for damp environments.
  • Detection area limitation strips are included for adjustment.
  • Accessories may be required for integration into switch ranges.
  • Mounting height and positioning affect detection area and performance.
  • KNX Data Secure ensures secure communication within the KNX network.
  • Always check compatibility with previous models during renovation.
Please accept cookies to help us improve this website Is this OK? Yes No More on cookies »